Technical Data
Input
- voltage: 100 V, 115 V or 230 V, ±10%, 50 Hz, max. 130 VA
Output
- voltage: continuously variable from 0 to ±260 V
- surge protection: 250 V
- current: max. 180 mA, electronically limited
- asymmetry of the output voltages: < 0.2 %
- output ripple and noise voltage: < 250 µVeff, < 2.5 mVpp (0.1Hz - 10kHz)
- line regulation: < 5 ppm at 10% change of the line voltage
- load regulation: < 100 ppm at 100% load change
- transient load regulation: 50 µs at 50 load change
- temperature coefficient of the output voltage: < 50 ppm/K
General
- input and output connectors: clamps
- cooling: external cooler
- fuses: external
- mounting by seven M3×12 mm spacer sleeves to fix the printed circuit board and one M6 spacer sleeve to fasten the mains transformer
- dimensions (length × width × height including spacer sleeves and wires): 225 × 140 × 70 mm3
- weight: 2.0 kg